MOLDED-CASE CIRCUIT BREAKER

Special Feature

30 ~ 225AF Small capacity
  • Easy panel production through unification of main dimensions - Handle Cutting Size : 24X52mm - Product Height : Uniform to 60mm
  • Improved breaking capacity : 35kA at AC460V(High blocking Type)
  • Compatible with New & Old Products
  • Easy Attachment
  • Acquired KS for all models
400 ~ 800AF Medium capacity
  • Improved breaking capacity - 400AF : 65kA at 460V(Korea type) - 800AF : 85kA at 460V(Korea type)
  • Expansion of model: Economic type, Standard type, High blocking type, Korea type
  • Sensitivity Current Selection Function(200,500mA)
  • MCCB remote control possible in combination with Attachment SHT (at the time of ground fault)
  • MCCB and image transformer (ZCT) all-in-one, greatly reducing material and labor costs
  • PANEL installation space reduction
  • Built-in ZCT passed the rigorous test of the Korea Fire Protection Agency
  • ONE TOUCH type coupling structure (ZCT withdrawal line)
  • Improved assembly and quality due to replacement of 600AF (3P, 4P)
  • Cost reduction and price competitiveness by reducing the size of 600AF (3P, 4P)
  • Added models from ELCB 400AF 3P to 600AF 3P, 4P
  • ZCT built-in 400AF (3P, 4P) to ZCT built-in 600AF (3P, 4P) models added
  • MCCB, ELCB, ZCT built-in MCCB same size
  • Increase use and convenience of user by adopting attachment cartridge method
  • The mounting hole position (44 × 194) is the same, so it can be replaced with 600AF.
  • External Size: 3P 140×257×103, 4P SIZE 3P: 184×257×103
  • Acquired NEP Certification

MOLDED-CASE CIRCUIT BREAKER(30AF ~225AF)

MOLDED-CASE CIRCUIT BREAKER(400AF ~800AF)

Economic

Economic Type DB-C Series

Rating

Frame Size 30AF 50AF
Type DB32Cb DB33Cb DB52Cb DB53Cb DB54Cb
Poles 2 3 2 3 4
ZCT built-in type     0
Rating Rating Current(In) A (5,10)(주1) 15, 20, 30 (5,10)15, 20, 30, 40, 50
Voltage(Ue) AC(V) 460 600
  DC(V) 125 250  
Insulation Voltage(Ui) V 460 690
RatingBreaking Current(Ka)
KS C 8321(Sym)
ICE60947-2(lcu)
lcs=0.5lcu
AC 600V - 5
480/500V - 7.5
460V (2.5)5 (5)10
415V 5 10
380V 5 14
220V (5)10 (10)25
DC 250V (5)10 5 -
125V - 10 -
Overcurrent trip Method Fully Electronic(ODP) Fully Electronic(ODP)
Attachment Auxiliary Contact AX - O
Alarm Contact AL - O
Voltage trip Device SHT - O
External Operation Handle DH(Surface attachment Type) - O
Terminal Cover   - O
Insulation Barrier   - O
External Size a 50 75 50 75 100
b 96 130
c 60 60
d 80 80
Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG
Acquisition Standard KS Certification / CE Certification KS Certification / CE Certification
Frame Size 60AF 100AF
Type DB62Cb DB63Cb DB64Cb DB102Cb DB103Cb DB104Cb
Poles 2 3 4 2 3 4
ZCT built-in type 0 0
Rating Rating Current(In) A 15, 20, 30, 40, 50, 60
15, 20, 30, 40, 50, 60, 75, 100
Voltage(Ue) AC(V) 600 600
  DC(V) 250 - 250 -
Insulation Voltage(Ui) V 690 690
RatingBreaking Current(Ka)
KS C 8321(Sym)
ICE60947-2(lcu)
lcs=0.5lcu
AC 600V 5 7.5
480/500V 7.5 10
460V 10 14
415V 10 14
380V 14 18
220V 25 25
DC 250V 5 - 7.5 -
125V 10 - 14 -
Overcurrent trip Method Fully Electronic(ODP) Fully Electronic(ODP)
Attachment Auxiliary Contact AX O O
Alarm Contact AL O O
Voltage trip Device SHT O O
External Operation Handle DH(Surface attachment Type) O O
Terminal Cover   O O
Insulation Barrier   O O
External Size a 50 75 100 50 75 100
b 130  
c 60  
d 80  
Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG
Acquisition Standard KS Certification / CE Certification KS Certification / CE Certification
Frame Size 225AF 400AF
Type DB202Cb DB203Cb DB204Cb DB402C DB403C DB404C
Poles 2 3 4 2 3 4
ZCT built-in type 0 0
Rating Rating Current(In) A 125, 150, 175, 200, 225
250, 300, 350, 400
Voltage(Ue) AC(V) 600 600
  DC(V) 250 - 250 -
Insulation Voltage(Ui) V 690 690
RatingBreaking Current(Ka)
KS C 8321(Sym)
ICE60947-2(lcu)
lcs=0.5lcu
AC 600V 7.5 18
480/500V 10 22
460V 18 30
415V 18 30
380V 18 30
220V 35 42
DC 250V 10 - 10 -
125V 15 - 20 -
Overcurrent trip Method Thermal Electronic(TM) Thermal Electronic(TM)
Attachment Auxiliary Contact AX O O
Alarm Contact AL O O
Voltage trip Device SHT O O
External Operation Handle DH(Surface attachment Type) O O
Terminal Cover   O O
Insulation Barrier   O O
External Size a 105 40 140 184
b 165 257
c 60 103
d 82.5 154
Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG
Acquisition Standard KS Certification / KS Certification / CE Certification   KS Certification /  (350,400A제외)CE Certification
Frame Size 600AF 630AF
Type DB602C DB603C DB604C DB632C DB633C DB634C
Poles 2 3 4 2 3 4
ZCT built-in type    
Rating Electric current(In) A 500, 600
500, 600
Voltage(Ue) AC(V) 600 600
  DC(V) 250 - 250 -
Insulation Voltage(Ui) V 690 690
RatingBreaking Current(Ka)
KS C 8321(Sym)
ICE60947-2(lcu)
lcs=0.5lcu
AC 600V 22 22
480/500V 25 25
460V 35 35
415V 35 35
380V 42 42
220V 50 50
DC 250V 20 - 20 -
125V 30 - 30 -
Overcurrent trip Method Thermal Electronic(TM) Thermal Electronic(TM)
Attachment Auxiliary Contact AX O O
Alarm Contact AL O O
Voltage trip Device SHT O O
External Operation Handle DH(Surface attachment Type) - -
Terminal Cover   - -
Insulation Barrier   O O
External Size a 210 280 140 184
b 275 257
c 103 103
d 149 154
Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG
Acquisition Standard KS Certification / KS Certification / CE Certification KS Certification /  KS(350,400A제외)CE Certification
Frame Size 800AF
Type DB802C DB803C DB804C
Poles 2 3 4
ZCT built-in type  
Rating Electric current(In) A 700, 800
Voltage(Ue) AC(V) 600
  DC(V) 250 -
Insulation Voltage(Ui) V 690
RatingBreaking Current(Ka)
KS C 8321(Sym)
ICE60947-2(lcu)
lcs=0.5lcu
AC 600V 22
480/500V 25
460V 35
415V 35
380V 42
220V 50
DC 250V 20 -
125V 30 -
Overcurrent trip Method Thermal Electronic(TM)
Attachment Auxiliary Contact AX O
Alarm Contact AL O
Voltage trip Device SHT O
External Operation Handle DH(Surface attachment Type) -
Terminal Cover   -
Insulation Barrier   O
External Size a 210 280
b 275
c 103
d 149
Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG
Acquisition Standard KS Certification / KS Certification / CE Certification

Standard

Standard Criteria
KS C 8321
IEC 60947-2
Approval & Certification
Electrical Appliance Safety Certification, KS, Korean Register of Shipping

※When ordering ZCT built-in type, please indicate "ZCT" after the basic model name.(example:DB104CB-ZCT)"

High-Breaking Type

High-Breaking Type DB-H Series

Rating

Frame Size 30AF 50AF
Type DB32Hb DB33Hb DB34Hb DB52Hb DB53Hb DB54Hb
Poles 2 3 4 2 3 4
ZCT built-in type 0 0
Rating Electric current(In) A 15, 20, 30 15, 20, 30, 40, 50
Voltage(Ue) AC(V) 600 600
  DC(V) 250 - 250 -
Insulation Voltage(Ui) V 690 690
Rating Breaking Current(Ka)
KS C 8321(Sym)
ICE60947-2(lcu)
lcs=0.5lcu
AC 600V 7.5 10
480/500V 10 14
460V 14 25
415V 14 25
380V 18 25
220V 25 50
DC 250V 7.5 - 14 -
125V 14 - 20 -
Overcurrent trip Method Fully Electronic(ODP) Thermal Electronic(TM)
Attachment Auxiliary Contact AX O O
Alarm Contact AL O O
Voltage trip Device SHT O O
External Operation Handle DH(Surface attachment Type) O O
Terminal Cover   O O
Insulation Barrier   O O
External Size a 50 75 100 60 90 120
b 130 155
c 60 60
d 80 80
Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG
Acquisition Standard KS Certification / CE Certification KS Certification / CE Certification
Frame Size 100AF 225AF
Type DB102Hb DB103Hb DB104Hb DB202Hb DB203Hb DB204Hb
Poles 2 3 4 2 3 4
ZCT built-in type 0 0
Rating Electric current(In) A 15, 20, 30, 40, 50, 60, 75, 100
100, 125, 150, 175, 200, 225
Voltage(Ue) AC(V) 600 600
  DC(V) 250 - 250 -
Insulation Voltage(Ui) V 690 690
Rating Breaking Current(Ka)
KS C 8321(Sym)
ICE60947-2(lcu)
lcs=0.5lcu
AC 600V 18 18
480/500V 25 25
460V 35 35
415V 35 35
380V 35 35
220V 65 65
DC 250V 18 - 18 -
125V 25 - 25 -
Overcurrent trip Method Thermal Electronic(TM) Thermal Electronic(TM)
Attachment Auxiliary Contact AX O O
Alarm Contact AL O O
Voltage trip Device SHT O O
External Operation Handle DH(Surface attachment Type) O O
Terminal Cover   O O
Insulation Barrier   O O
External Size a 60 90 120 105 140
b 155 165
c 60 60
d 80 82.5
Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG
Acquisition Standard KS Certification / CE Certification KS Certification /
Frame Size 400AF
Type DB402H DB403H DB404H
Poles 2 3 4
ZCT built-in type 0
Rating Rating Current(In) A 250, 300, 350, 400
Voltage(Ue) AC(V) 600
  DC(V) 250 -
Insulation Voltage(Ui) V 690
Rating Breaking Current(Ka)
KS C 8321(Sym)
ICE60947-2(lcu)
lcs=0.5lcu
AC 600V 25
480/500V 35
460V 50
415V 50
380V 65
220V 85
DC 250V 40 -
125V 50 -
Overcurrent trip Method Thermal Electronic(TM)
Attachment Auxiliary Contact AX O
Alarm Contact AL O
Voltage trip Device SHT O
External Operation Handle DH(Surface attachment Type) -
Terminal Cover   0
Insulation Barrier   O
External Size a 140 184
b 257
c 95
d 154
Download PDF Download DWG Download PDF Download DWG Download PDF Download DWG
Acquisition Standard KS Certification / KS Certification / CE Certification

Standard

Standard Criteria
KS C 8321
IEC 60947-2
Approval & Certification
Electrical Appliance Safety Certification, KS, Korean Register of Shipping

※When ordering ZCT built-in type, please indicate "ZCT" after the basic model name.(example:DB104CB-ZCT)"